Filter driers and drier cores: when to fit and how to choose
What a filter drier and a replaceable drier core do, when to replace them and how to choose the right size and connection.
Related products
Why moisture is the enemy
Even small amounts of water in a refrigerant circuit react with refrigerant and oil to form acids, which corrode copper, break down the oil and freeze at the expansion device. A filter drier removes moisture and acid with a desiccant and traps solid debris with a screen or filter block, so the expansion valve and compressor see clean, dry refrigerant.
What is inside a filter drier
The desiccant is usually a molecular sieve, sometimes blended with activated alumina. The sieve captures water and the alumina helps to hold acids. The refrigerant oils used with R410A, R32 and R134a absorb moisture from the air very quickly, so the drier must be made for those refrigerants and oils. Always check that the drier is rated for the refrigerant in the system.
Sealed driers and replaceable cores
- A filter drier is a sealed shell brazed or flared into the line. When it is spent, the whole drier is replaced.
- A replaceable-core system uses a service shell that stays in the line. Only the core, such as the Klima Drier Core 48-DC, is changed.
When to replace
- Whenever the refrigerant circuit is opened for service
- After every compressor replacement
- After a compressor burnout, using a suction-line drier with acid-removing desiccant, then a new liquid-line drier once the acid test is clear
- When the moisture indicator shows wet, or the drier is blocked
Choosing size and connection
- Match the connection size and style (flare or solder) to the line. Do not reduce the line to suit the drier.
- Choose capacity for the system size and refrigerant. A larger drier is safe, and an undersized one restricts flow.
- Use a bi-flow drier on reversible heat pumps, because refrigerant flows in both directions.
- Check that the pressure rating suits R410A or R32 where those refrigerants are used.
Where to fit it
- A liquid-line drier goes on the liquid line after the condenser and receiver, ahead of the sight glass and the metering device, so everything downstream sees filtered, dry refrigerant.
- A suction-line drier is fitted for burnout cleanup, or where the equipment maker requires it. It protects the compressor but adds pressure drop, so measure the drop across it and remove it when the system is clean.
Cleaning up after a compressor burnout
- Recover the refrigerant and remove the failed compressor and the old drier.
- Test the oil for acid. If it is acidic, clean or replace the lines and components as the equipment maker advises.
- Fit the new compressor, a suction-line drier with acid-removing desiccant and a new liquid-line drier.
- Evacuate, charge and run the system. After the first hours of running, measure the pressure drop across the suction drier and test the oil again.
- Change the oil and the driers again if the acid test is positive. Remove the suction-line drier once the system is clean if the maker specifies it.
Signs of a blocked drier
- Frost or a cold patch on the drier body
- Bubbles in the sight glass despite a correct charge
- Low suction pressure with a warm drier outlet compared with its inlet, meaning a temperature drop across the drier
Checking a drier in service
- Measure the pipe temperature on each side of the drier. A difference of more than a couple of kelvin points to a restriction.
- Watch the sight glass. A moisture indicator changes colour when the refrigerant is wet. The colour chart is printed on the glass and the colours differ between makers. Judge it only after the system has run for some hours.
- Look for frost, a cold patch or oil staining on the shell.
Fitting tips
Keep the new drier sealed until the moment of fitting, because the desiccant begins to absorb humidity as soon as it is open. Follow the flow arrow, protect the shell from overheating when you braze, and evacuate the system to a deep vacuum before charging.
Questions about filter driers
Can I reuse a drier that was already opened?
No. The desiccant starts to absorb moisture as soon as the seal is broken, and once it is saturated it cannot protect the system. Keep the new drier sealed until the circuit is ready for it.
Does the flow direction matter?
Yes. Fit the drier with the flow arrow pointing the way the refrigerant moves, unless it is a bi-flow drier made for heat pumps. A drier fitted backwards can restrict the flow.
Should I fit a bigger drier to be safe?
A drier one size larger on the same connection is safe and holds more moisture. A drier that is too small restricts the flow and saturates early. Do not change the pipe size to suit the drier.
How often must a drier be replaced?
Whenever the circuit is opened and after any compressor change. A sealed system that is never opened can run for years, but check the sight glass and the temperature drop across the drier at each service.