Klima Industries

Superheat and subcooling: measuring with the right thermometer

How superheat and subcooling are calculated, which tools you need and how to avoid the common measurement mistakes.

Related products

What the two numbers tell you

Superheat and subcooling show whether a system has the right refrigerant charge and whether the metering device is doing its job.

  • Superheat is the suction-line temperature minus the evaporating temperature. It shows how far the refrigerant vapour has been heated above its boiling point at the evaporator outlet.
  • Subcooling is the condensing temperature minus the liquid-line temperature. It shows how far the liquid has been cooled below its condensing point at the condenser outlet.

The evaporating and condensing temperatures are not measured directly. You read suction and discharge pressure on a gauge manifold and convert each pressure to a saturation temperature with the pressure-temperature chart for the refrigerant in the system.

Tools you need

  • A gauge manifold with the correct refrigerant scale
  • Two accurate pipe-clamp or surface thermometers, one for the suction line and one for the liquid line
  • Insulation to cover each sensor, so air does not affect the reading

Steps

  1. Run the system for ten to fifteen minutes so that pressures and temperatures stabilise.
  2. Read suction and discharge pressure and convert them to saturation temperatures.
  3. Clamp a sensor on clean copper on the suction line, near the outlet of the evaporator or at the compressor, and cover it with insulation.
  4. Clamp the second sensor on the liquid line near the condenser outlet, and cover it too.
  5. Calculate superheat and subcooling and compare them with the targets on the unit data plate or in the manual.

A worked example

This example uses R410A. The numbers are for illustration. Always read your own gauges and use the pressure-temperature scale for your refrigerant.

ReadingValueResult
Suction pressure8.3 bar (gauge)Evaporating temperature about 5 °C
Suction-line temperature12 °CSuperheat = 12 ? 5 = 7 K
Liquid pressure26.3 bar (gauge)Condensing temperature about 45 °C
Liquid-line temperature38 °CSubcooling = 45 ? 38 = 7 K

Reading the pattern

What you seeLikely meaning
High superheat and low subcoolingLow refrigerant charge, or a leak
Low superheat and high subcoolingOvercharge, or too much liquid held in the condenser
High superheat and high subcoolingA restriction in the liquid line, the drier or the metering device
Low superheat and low suction pressurePoor evaporator airflow, a dirty filter or a frozen coil

These patterns point to causes. They do not prove them, so check airflow, coil cleanliness and the metering device before you add or remove refrigerant.

Targets

The target depends on the metering device and on the manufacturer, so always use the value on the data plate or in the manual. Fixed-orifice systems usually use a charging chart based on indoor and outdoor conditions, while systems with a thermostatic expansion valve are normally charged to a subcooling value. As a rough orientation, many systems run with single-digit kelvin values for both.

Inverter systems and systems with electronic expansion valves often need a special charging mode or a fixed compressor speed. Follow the maker’s procedure for those, because the usual charging chart may not apply.

Common mistakes

  • Poor contact between the sensor and the pipe, or no insulation over the sensor
  • Measuring before the system is stable, or with a dirty coil or low airflow
  • Using the wrong refrigerant scale on the gauge
  • A thermometer that has not been checked recently; test it in an ice-water bath, which should read about 0 °C

Why the readings drift

  • A thermostatic expansion valve that is hunting makes superheat swing up and down. Allow more time to settle, then check that the bulb is clamped tight and insulated.
  • The load or the outdoor temperature changed during the test.
  • Dirty filters or coils changed the airflow.
  • Air or other non-condensable gas in the system raises the condensing pressure and gives a false picture of the charge.

Questions about superheat and subcooling

Can I charge a system by pressure alone?

No. Pressures change with the indoor load and the outdoor temperature, so the same charge can read very differently from one day to the next. Use superheat or subcooling, or weigh in the charge when the maker specifies it.

How long should I wait after adding or removing refrigerant?

Wait until pressures and temperatures stop moving, which usually takes at least ten to fifteen minutes, then measure again before you adjust further.

What is a normal superheat or subcooling value?

There is no single value. It depends on the metering device, the refrigerant and the manufacturer. Use the figure on the data plate or in the installation manual.

Do I need a special thermometer?

A pipe-clamp thermometer with good contact and an accuracy of about ±0.5 K is enough for most work. Check it in an ice-water bath, which should read about 0 °C, before you rely on it.