A refrigerant circuit works safely only inside a pressure window. If condenser airflow fails, discharge pressure can spike and threaten the compressor and pipework. If refrigerant leaks or a filter blocks, suction pressure can fall so far that the evaporator ices up and the compressor loses the cooling that comes with returning gas. Pressure switches watch for both conditions and open the control circuit before damage occurs.

Klima Pressure Switches come as high-pressure (HP) switches, low-pressure (LP) switches and combined dual units. Fixed and adjustable settings are listed per model, with automatic or manual reset, flare or capillary connection and contact rating. Manual-reset HP switches are common for safety duty because they keep the unit off until a technician has found the cause.

Klima Pressure Switches stop the compressor when discharge pressure climbs too high or suction pressure falls too low. Models are listed by pressure range, differential, reset type and connection so you can match them to the refrigerant and the circuit.

Models

Related products

Supply notes by country

How pressure switches are chosen and used in each country, with notes for its cities.

Key features

  • HP, LP and dual types. One family for high-side protection, low-side protection and combined control.
  • Adjustable and fixed settings. Choose a preset cut-out or fine-tune within the range.
  • Automatic and manual reset. Manual reset keeps a tripped unit off until it has been inspected.
  • Refrigerant compatibility. Models listed for common HFC refrigerants, with notes for higher-pressure R410A and R32 duty.
  • Connections. Flare and capillary connections for different service-valve and pipe layouts.
  • Contact ratings. Rated to switch contactor coils and small loads directly.

Where pressure switches are used

  • Split, VRF and packaged air conditioners
  • Condensing units and cold rooms
  • Chillers and air-cooled condensers
  • Heat pump outdoor units
  • Supermarket racks and display cases
  • Refrigerated transport and containers
  • Ice machines and process cooling
  • Water-cooled condensers and cooling-tower circuits
  • Fan speed control by head pressure

How to choose pressure switches

  • Choose the refrigerant and its pressure range first, because cut-out values for R410A differ greatly from those for R22 or R134a.
  • Use an HP switch with manual reset for safety duty and an LP switch with automatic reset for pump-down or control duty.
  • Take the setting from the compressor or unit manual and stay below the design pressure of the weakest component.
  • Match the connection (flare size or capillary) to the service port you will use.
  • Check the electrical rating against the contactor coil or control circuit it will switch.

Care and maintenance

  • Test cut-out and cut-in values with a gauge manifold and nitrogen or a controlled pressure source at commissioning.
  • Check that connections are leak-free and that capillary tubes are not kinked.
  • Replace a switch that fails to trip at the specified pressure, and do not adjust a safety switch beyond its marked range.

Common faults

  • Frequent unexplained compressor lockouts
  • A unit that does not restart after a trip
  • A switch that cycles at the wrong pressure

Questions about pressure switches

What does a high pressure switch do?

It opens the control circuit if discharge pressure rises above a set limit, which stops the compressor before the pressure can damage it or the pipework.

What does a low pressure switch do?

It stops the compressor when suction pressure falls too low, protecting it from running with too little refrigerant and preventing evaporator icing.

What is a dual pressure switch?

One body with both high- and low-pressure sensing and a combined contact, so a single connection protects both sides of the circuit.

Should I choose manual or automatic reset?

Choose manual reset for safety (HP) duty, because it forces a technician to investigate. Automatic reset suits low-pressure control such as pump-down.

How do I set the cut-out pressure?

Take the value from the equipment manual for the refrigerant in use and verify it with a gauge set. Never set a switch above the pressure rating of the components it protects.

Can I use the same switch for R22 and R410A?

Only if its pressure range and rating cover both. R410A runs at much higher pressures, so check the model list before you order.