Klima Industries

Klima High Pressure Switch, Manual Reset

High pressure switch with manual reset for refrigerant circuits.

Klima Pressure Switches (High & Low) ยท Model KPS-H32M

About this pressure switch

A high-pressure switch is the last defence of a refrigeration compressor against excessive discharge pressure, which can follow a failed condenser fan, a blocked or dirty coil or an overcharge. This model has an adjustable range from 8 to 32 bar with a 3 bar differential and a manual reset, a 10 A contact at 250 V AC and a 1/4 in SAE flare connection, and it is listed for HFC refrigerants.

Manual reset is deliberate: once the switch has tripped, it stays tripped until somebody presses the reset button, which means the cause has to be found before the compressor runs again. Safety rules for refrigerating systems, such as EN 12263 for pressure-limiting switching devices, commonly call for a lock-out on high pressure, so check the standard that applies to your plant. Set it below the maximum allowable pressure on the system's nameplate and below the setting of any relief valve, and note that R410A and R32 systems work at higher pressures than R134a or R404A.

Specifications

SpecificationValue
ModelKPS-H32M
TypeHigh pressure
Pressure range8 to 32 bar
Cut-out settingAdjustable bar
Differential3 bar
ResetManual
Contact rating10 A at 250 V AC
Connection1/4 in SAE flare
RefrigerantsHFC refrigerants

Where it fits

  • Safety cut-out on the high side of split, packaged and condensing units
  • Refrigeration systems whose standard requires a lock-out on high pressure
  • Replacement of a tripped or failed high-pressure control
  • Plant where a service call after a trip is preferable to automatic restart

Fitting and checking

Connect the switch to the discharge line or the high-side port through its 1/4 in flare, and wire the contact in the control circuit, in series with the contactor coil. Set the cut-out with a gauge manifold: raise the pressure by blocking condenser air in a controlled test and check that the switch trips at the set value. Record the setting on the nameplate or the service sheet, and press the reset to confirm it operates.

Compared with the other pressure switches

The 4 models in Klima Pressure Switches (High & Low) differ mainly in type, pressure range and differential. Every model in the family has the same cut-out setting (Adjustable bar), contact rating (10 A at 250 V AC), connection (1/4 in SAE flare) and refrigerants (HFC refrigerants), so the choice comes down to the values above.

SpecificationThis modelAcross the range
TypeHigh pressureHigh pressure / Low pressure / Dual HP/LP
Pressure range8 to 32 bar8 to 32 / -0.7 to 7 / HP 8 to 32, LP -0.7 to 7
Differential3 bar3 / 0.5 to 4
ResetManualManual / Automatic / Manual HP, automatic LP

The closest alternative in the range is Klima High Pressure Switch, Auto Reset, which shares 7 of the 8 listed specifications and differs in reset. Quote the model code KPS-H32M when you enquire.

Questions

Why choose manual rather than automatic reset?

A trip on high pressure means something is wrong. Manual reset stops the compressor from cycling on and off against a fault until a technician has looked at it.

How do I choose the cut-out setting?

Use the system's maximum allowable pressure from the nameplate and keep the setting below it, and below any relief valve. Confirm that the range of the switch covers the value you need.

Selection, care and fault-finding notes for the whole family are on the Klima Pressure Switches (High & Low) page, and the contact page takes enquiries with the model code KPS-H32M. For background reading, see the guide High and low pressure switches: settings and protection explained.