Klima High Pressure Switch, Auto Reset
High pressure switch with automatic reset for refrigerant circuits.
Klima Pressure Switches (High & Low) ยท Model KPS-H32A
About this pressure switch
This high-pressure switch has the same 8 to 32 bar range, 3 bar differential, 10 A contact at 250 V AC and 1/4 in SAE flare connection as the manual-reset model, but resets by itself once the pressure has fallen by the differential. It is meant for systems where a high-pressure trip is a temporary condition that clears on its own, such as a condenser fan that cycles or a hot afternoon that pushes the head pressure up, and where a technician is not on hand to reset it.
The convenience has a cost: a system that trips and restarts repeatedly is working against a fault, and every cycle stresses the compressor. Use auto reset as a control function, or where the standard allows it, and not as a replacement for a lock-out safety device. A good arrangement is an auto-reset switch for ordinary control and a separate manual-reset switch set slightly higher as the safety cut-out.
Specifications
| Specification | Value |
|---|---|
| Model | KPS-H32A |
| Type | High pressure |
| Pressure range | 8 to 32 bar |
| Cut-out setting | Adjustable bar |
| Differential | 3 bar |
| Reset | Automatic |
| Contact rating | 10 A at 250 V AC |
| Connection | 1/4 in SAE flare |
| Refrigerants | HFC refrigerants |
Where it fits
- Pressure control of condenser fans and unloading on the high side
- Systems where short trips on hot days are expected and are not faults
- Unattended plant where a manual reset would mean a long outage
- Secondary high-pressure protection alongside a manual-reset safety switch
Fitting and checking
Mount the switch on the high-side port, wire the contact in the control circuit and set the cut-out with gauges. The differential decides the cut-in point: with a 3 bar differential and a cut-out at 26 bar, the switch resets at about 23 bar. After setting, watch the system through a few cycles and make sure the trip does not repeat more than a few times per hour, which would indicate a fault to be fixed.
Compared with the other pressure switches
This model is one of 4 in Klima Pressure Switches (High & Low); what changes from one to the next is type, pressure range and differential. Every model in the family has the same cut-out setting (Adjustable bar), contact rating (10 A at 250 V AC), connection (1/4 in SAE flare) and refrigerants (HFC refrigerants), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Type | High pressure | High pressure / Low pressure / Dual HP/LP |
| Pressure range | 8 to 32 bar | 8 to 32 / -0.7 to 7 / HP 8 to 32, LP -0.7 to 7 |
| Differential | 3 bar | 3 / 0.5 to 4 |
| Reset | Automatic | Manual / Automatic / Manual HP, automatic LP |
The closest alternative in the range is Klima High Pressure Switch, Manual Reset, which shares 7 of the 8 listed specifications and differs in reset. Quote the model code KPS-H32A when you enquire.
Questions
Is an auto-reset switch safe as the only high-pressure protection?
Not usually. Where a standard requires a lock-out safety cut-out, use a manual-reset device. Auto reset suits control duty or secondary protection.
What does the 3 bar differential do?
It is the difference between the cut-out and the reset pressure. The switch trips at the set pressure and closes again when the pressure falls by 3 bar.
Selection, care and fault-finding notes for the whole family are on the Klima Pressure Switches (High & Low) page, and the contact page takes enquiries with the model code KPS-H32A. For background reading, see the guide High and low pressure switches: settings and protection explained.