High and low pressure switches: settings and protection explained
What HP and LP switches protect against, how manual and automatic reset differ and how to set and test them.
Related products
What pressure switches protect
A refrigerant circuit is safe only inside a pressure window. A high-pressure (HP) switch opens the control circuit when discharge pressure climbs too high. A low-pressure (LP) switch opens it when suction pressure falls too low. Wired in the control circuit, they drop out the contactor before the compressor or the pipework is damaged.
Cut-out, cut-in and differential
Three terms appear on switch labels and in manuals. On a high-pressure switch the cut-out is the higher value, and on a low-pressure switch it is the lower one.
- Cut-out is the pressure at which the switch opens the control circuit and stops the compressor.
- Cut-in is the pressure at which the switch closes again, where it resets automatically.
- Differential is the gap between cut-out and cut-in. A narrow differential cycles the compressor more often, and a wide one lets the pressure swing further.
Why pressure goes out of range
- High pressure: a failed condenser fan, a dirty condenser coil, overcharge, air or other non-condensable gas in the system, or a blocked discharge line.
- Low pressure: a refrigerant leak, a blocked filter drier or expansion valve, poor evaporator airflow or a frozen coil.
Manual and automatic reset
- A manual-reset switch stays open after a trip until someone presses the reset button, so a technician has to look for the cause. It is the usual choice for HP safety duty.
- An automatic-reset switch closes again when pressure returns to a safe value. It suits LP control and pump-down duty.
Setting the switch
Take the cut-out and cut-in values from the equipment manual for the refrigerant in use, and stay below the design pressure of the weakest component. R410A systems run at about one and a half times the pressure of R22, so a switch chosen for R22 will not suit them. Do not adjust a safety switch beyond its marked range.
Choosing the high-pressure setting
Start from the lowest design pressure of any part on the high side, usually printed as PS on the compressor, condenser or receiver nameplate. The cut-out must be at or below that value, and above the highest pressure that the system reaches on the hottest day, with margin. Otherwise the unit trips when it is needed most.
Wiring
Wire the switches in series with the contactor coil, using the contacts that are closed in the safe state, so that any trip, loose wire or broken switch drops out the contactor. Never bridge a safety switch to get a unit running.
Low-pressure switches, pump-down and freeze protection
On a system with pump-down control, the low-pressure switch ends the pump-down by stopping the compressor once the evaporator has been emptied. On other systems it protects against a lost charge, because a compressor that runs without enough returning refrigerant loses motor cooling and oil return. A cut-out set too high causes nuisance trips on cool mornings, and one set too low lets the evaporator freeze or the compressor run starved.
Testing at commissioning
- Connect a gauge manifold to the service ports.
- For an HP switch, raise discharge pressure in a controlled way, for example by restricting condenser airflow, and note the pressure at which the unit stops.
- For an LP switch, throttle the suction side or pump down and note the cut-out.
- Compare the readings with the set values and adjust or replace the switch if it is off.
Nuisance trips: what to check first
- Condenser airflow: the fan runs in the right direction, the coil is clean and nothing blocks the air.
- Refrigerant charge, judged by superheat and subcooling and not by pressure alone.
- A blocked drier, expansion valve or liquid line.
- Evaporator airflow: dirty filters, a frozen coil or a slow blower.
- Only then the switch itself, tested against a reference gauge.
Fault finding
- A unit that locks out repeatedly points to the cause of the pressure problem, not to the switch.
- A unit that never restarts after a trip may have a manual-reset switch waiting to be reset.
- A switch that trips at the wrong pressure needs testing against a reference gauge and replacing if it has drifted.
Questions about pressure switches
Can one switch handle both high and low pressure?
Yes. A dual pressure switch has a high-pressure element and a low-pressure element in one body, each with its own setting. Separate switches are used where the two functions need different reset types or locations.
Why is a high-pressure switch usually manual reset?
A high-pressure trip means that something is wrong, such as a failed fan or a blocked coil. A manual reset makes sure that a technician looks for the cause instead of letting the compressor cycle against the fault.
Is it safe to bypass a tripped switch to keep the unit running?
No. The switch is the last protection for the compressor and for people working near the pipework. Find and fix the cause of the trip.
How often should the switches be tested?
At commissioning, and then as part of the planned service. Test each switch against a reference gauge and record the cut-out value.