Klima Industries

Klima Dual Pressure Switch, HP/LP

Dual HP/LP pressure switch with a manual-reset high side and an automatic-reset low side for refrigerant circuits.

Klima Pressure Switches (High & Low) ยท Model KPS-D

About this pressure switch

The dual pressure switch combines a high-pressure and a low-pressure switch in one housing, which saves a mounting position and some wiring. The high-pressure side has a range of 8 to 32 bar with manual reset and the low-pressure side a range of -0.7 to 7 bar with automatic reset. It has a 10 A contact at 250 V AC and a 1/4 in SAE flare connection, and is listed for HFC refrigerants.

Because both functions sit in one housing, follow the maker's connection layout so that each function senses the correct side of the circuit before you plan the piping. Wired in series with the contactor coil, the switch opens the control circuit on either a high or a low pressure condition, so one pair of wires to the contactor is enough.

Specifications

SpecificationValue
ModelKPS-D
TypeDual HP/LP
Pressure rangeHP 8 to 32, LP -0.7 to 7 bar
Cut-out settingAdjustable bar
ResetManual HP, automatic LP
Contact rating10 A at 250 V AC
Connection1/4 in SAE flare
RefrigerantsHFC refrigerants

Where it fits

  • Combined high and low pressure protection on condensing units and chillers
  • Packaged equipment with limited mounting space
  • Replacement of two separate pressure switches in a single housing
  • OEM-style installations where one control covers both pressure limits

Fitting and checking

Mount the switch and make the pressure connection as the datasheet shows, then wire the contact in series with the contactor coil. Set the high-pressure cut-out below the system's maximum allowable pressure and the low-pressure cut-out above atmospheric pressure. Test each function separately: block the condenser to check the high-pressure trip and close the liquid line to check the low-pressure cut-out.

Compared with the other pressure switches

The 4 models in Klima Pressure Switches (High & Low) differ mainly in type, pressure range and reset. Every model in the family has the same cut-out setting (Adjustable bar), contact rating (10 A at 250 V AC), connection (1/4 in SAE flare) and refrigerants (HFC refrigerants), so the choice comes down to the values above.

SpecificationThis modelAcross the range
TypeDual HP/LPHigh pressure / Low pressure / Dual HP/LP
Pressure rangeHP 8 to 32, LP -0.7 to 7 bar8 to 32 / -0.7 to 7 / HP 8 to 32, LP -0.7 to 7
ResetManual HP, automatic LPManual / Automatic / Manual HP, automatic LP

The closest alternative in the range is Klima High Pressure Switch, Manual Reset, which shares 4 of the 8 listed specifications and differs in type, pressure range and reset. Quote the model code KPS-D when you enquire.

Questions

What happens when the high-pressure side trips?

The contact opens and stays open until the manual reset button is pressed, so the compressor remains off until a technician has checked the cause.

Can I replace two switches with this one?

Yes, if its pressure ranges and connection suit your system. Check the datasheet for the wiring and the connection layout.

Selection, care and fault-finding notes for the whole family are on the Klima Pressure Switches (High & Low) page, and the contact page takes enquiries with the model code KPS-D. For background reading, see the guide High and low pressure switches: settings and protection explained.