Klima Low Pressure Switch, Auto Reset
Low pressure switch with automatic reset for refrigerant circuits.
Klima Pressure Switches (High & Low) ยท Model KPS-L7A
About this pressure switch
A low-pressure switch protects the compressor from running with too little refrigerant, which can follow a leak, a blocked filter drier or a frozen evaporator. This model covers a range from -0.7 to 7 bar, with an adjustable differential from 0.5 to 4 bar, automatic reset, a 10 A contact at 250 V AC and a 1/4 in SAE flare connection, for HFC refrigerants.
On a low-temperature system, loss of charge shows first as a falling suction pressure. Set the cut-out well above atmospheric pressure so that the compressor stops before the circuit goes into vacuum: a system that draws air through a leak is contaminated with moisture, and the compressor, which is cooled by suction gas, can overheat. Where a pump-down cycle is used, the same switch can end the pump-down at the chosen suction pressure.
Specifications
| Specification | Value |
|---|---|
| Model | KPS-L7A |
| Type | Low pressure |
| Pressure range | -0.7 to 7 bar |
| Cut-out setting | Adjustable bar |
| Differential | 0.5 to 4 bar |
| Reset | Automatic |
| Contact rating | 10 A at 250 V AC |
| Connection | 1/4 in SAE flare |
| Refrigerants | HFC refrigerants |
Where it fits
- Loss-of-charge protection on cold rooms, display cabinets and condensing units
- Pump-down control on systems with a liquid-line solenoid valve
- Protection against evaporator freeze-up on air conditioning units
- Low-side protection on packaged and split systems
Fitting and checking
Fit the switch on the suction line or a low-side port, and wire its contact in series with the contactor coil. Set the cut-out and the differential with a gauge manifold: for a pump-down system the cut-in is set to restart the compressor when the pressure rises after the solenoid opens. Check the setting by closing the liquid line slowly and watching the pressure at which the compressor stops.
Compared with the other pressure switches
The 4 models in Klima Pressure Switches (High & Low) differ mainly in type, pressure range and differential. Every model in the family has the same cut-out setting (Adjustable bar), contact rating (10 A at 250 V AC), connection (1/4 in SAE flare) and refrigerants (HFC refrigerants), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Type | Low pressure | High pressure / Low pressure / Dual HP/LP |
| Pressure range | -0.7 to 7 bar | 8 to 32 / -0.7 to 7 / HP 8 to 32, LP -0.7 to 7 |
| Differential | 0.5 to 4 bar | 3 / 0.5 to 4 |
| Reset | Automatic | Manual / Automatic / Manual HP, automatic LP |
The closest alternative in the range is Klima High Pressure Switch, Auto Reset, which shares 5 of the 8 listed specifications and differs in type, pressure range and differential. Quote the model code KPS-L7A when you enquire.
Questions
Why must the low-pressure cut-out stay above atmospheric pressure?
A cut-out at or below atmospheric pressure allows air and moisture to be drawn into a leaking system, and the compressor can overheat running at very low suction.
What does the differential do?
It sets how far the pressure must rise after a cut-out before the switch restarts the compressor. The adjustable differential of 0.5 to 4 bar lets you avoid short cycling.
Selection, care and fault-finding notes for the whole family are on the Klima Pressure Switches (High & Low) page, and the contact page takes enquiries with the model code KPS-L7A. For background reading, see the guide High and low pressure switches: settings and protection explained.