Klima 3-Core Flexible Cable 1.5 mm²
3-core flexible copper cable, 1.5 mm² per core, PVC insulated, for air conditioner interconnecting and power wiring.
Klima Cables (3 & 4 Core) · Model KCB-3C15
About this cable
A three-core cable carries live, neutral and earth, which makes the 1.5 mm² size the light-duty member of the range: small indoor units, fan coil units, ventilation fans, condensate pumps and control wiring. The conductors are copper with PVC insulation and sheath, rated 300/500 V, and the cable is supplied in 100 m coils with colour-coded cores.
At 1.5 mm² the main limit is usually voltage drop rather than heating. For a copper cable of this size a typical figure is about 29 mV per ampere per metre, so a 6 A load 15 m away loses 29 × 6 × 15 ÷ 1000 ? 2.6 V, about 1.1 % of 230 V. Longer runs or higher currents change that quickly, which is why the larger sizes exist.
Specifications
| Specification | Value |
|---|---|
| Model | KCB-3C15 |
| Cores | 3 |
| Conductor size | 1.5 mm² |
| Insulation | PVC |
| Voltage rating | 300/500 V |
| Length per coil | 100 m |
| Core colours | Colour-coded cores |
Where it fits
- Power supply to small indoor units, cassettes and fan coil units
- Wiring for condensate pumps, extractor fans and small ventilation fans
- Control and thermostat wiring on mains-voltage circuits
- Short links between isolators and equipment inside a plant room
Fitting and checking
Check the load current and the cable length against the datasheet and the local wiring regulations, which set the permitted current for each installation method. Run cable in conduit or trunking outdoors and where it can be knocked; a PVC sheath is not designed for continuous sunlight. Strip conductors cleanly without nicking the copper, and use ferrules or crimp terminals so that every strand is held.
Compared with the other cables
This model is one of 6 in Klima Cables (3 & 4 Core); what changes from one to the next is cores and conductor size. Every model in the family has the same insulation (PVC), voltage rating (300/500 V), length per coil (100 m) and core colours (Colour-coded cores), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Cores | 3 | 3 to 4 |
| Conductor size | 1.5 mm² | 1.5 to 4 mm² |
This is the smallest model in the range by conductor size. The next step up is Klima 3-Core Flexible Cable 2.5 mm² (2.5 mm²). Quote the model code KCB-3C15 when you enquire so that the right size is supplied.
Questions
Is 1.5 mm² enough for a split-system outdoor unit?
It depends on the unit's current, the cable length and the local regulations. For small units over short runs it may be acceptable; for larger units or longer runs use 2.5 mm² or 4 mm². Always follow the manufacturer's installation manual.
What do the colour-coded cores mean?
Each core colour has a defined role, such as live, neutral or earth. Colours differ between regions, so check the local wiring code before connecting.
Selection, care and fault-finding notes for the whole family are on the Klima Cables (3 & 4 Core) page, and the contact page takes enquiries with the model code KCB-3C15.