3-core flexible copper cable, 4 mm² per core, PVC insulated, for air conditioner interconnecting and power wiring.
Klima Cables (3 & 4 Core) · Model KCB-3C4
About this cable
The 4 mm² three-core cable is for the heavier single-phase loads and for longer runs, where a smaller conductor would waste too much voltage in the cable. It carries live, neutral and earth to larger outdoor units, to groups of fans and to single-phase equipment that starts under heavy load. The copper conductors have a PVC insulation and sheath rated 300/500 V, in 100 m coils with colour-coded cores.
The advantage of 4 mm² shows up over distance. A typical figure is about 11 mV per ampere per metre, so a 16 A load 30 m away loses 11 × 16 × 30 ÷ 1000 ? 5.3 V, about 2.3 % of 230 V; at 2.5 mm² the same run would lose about 8.6 V (3.8 %). Reduced voltage at the compressor terminals increases starting current and heat, so a thicker cable on a long run protects the compressor.
Specifications
| Specification | Value |
|---|---|
| Model | KCB-3C4 |
| Cores | 3 |
| Conductor size | 4 mm² |
| Insulation | PVC |
| Voltage rating | 300/500 V |
| Length per coil | 100 m |
| Core colours | Colour-coded cores |
Where it fits
- Outdoor units of larger single-phase split and packaged systems
- Long supply runs from the distribution board to rooftop or ground-level units
- Immersion and electric heater circuits and pump sets on one phase
- Feeder to a sub-panel in a plant room
Fitting and checking
Check that the terminals of the equipment accept a 4 mm² conductor; some small terminals need a ferrule or a crimp lug of suitable size. Use cable glands that suit the outer diameter, and tighten them so that the sheath is gripped without crushing it. When planning a run, remember that a 100 m coil is cut to length, so measure the route including the bends and the drops at each end.
Compared with the other cables
Across the 6 models in Klima Cables (3 & 4 Core), the values that vary are cores and conductor size. Every model in the family has the same insulation (PVC), voltage rating (300/500 V), length per coil (100 m) and core colours (Colour-coded cores), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Cores | 3 | 3 to 4 |
| Conductor size | 4 mm² | 1.5 to 4 mm² |
This is the largest model in the range by conductor size. The next step down is Klima 3-Core Flexible Cable 2.5 mm² (2.5 mm²). Quote the model code KCB-3C4 when you enquire so that the right size is supplied.
Questions
When should I use 4 mm² instead of 2.5 mm²?
When the load current is high, the run is long or the voltage-drop calculation exceeds the limit. A thicker cable also runs cooler, which helps where it is bundled with others.
Does a thicker cable change the circuit breaker?
Not by itself. The breaker is chosen for the load and for the cable it protects; a larger cable allows a higher rating but does not require one.
Selection, care and fault-finding notes for the whole family are on the Klima Cables (3 & 4 Core) page, and the contact page takes enquiries with the model code KCB-3C4.