Klima Industries

Klima 4-Core Flexible Cable 1.5 mm²

4-core flexible copper cable, 1.5 mm² per core, PVC insulated, for air conditioner interconnecting and power wiring.

Klima Cables (3 & 4 Core) · Model KCB-4C15

About this cable

The fourth core makes the 1.5 mm² four-core cable the usual interconnecting cable between the indoor and outdoor unit of a split air conditioner, where it carries live, neutral, earth and a signal or control conductor. It is also used for three-phase control circuits and for motorised valves and actuators that need more than three conductors. The cores are copper with PVC insulation and sheath, rated 300/500 V, in 100 m coils with colour-coded cores.

The size suits low currents. For three-phase circuits the voltage drop is lower per ampere than for single-phase, about 25 mV per ampere per metre for 1.5 mm², so a 5 A load 20 m away loses 25 × 5 × 20 ÷ 1000 = 2.5 V of a 400 V supply, well under 1 %. Where a manufacturer specifies the interconnect cable for a model, follow that specification.

Specifications

SpecificationValue
ModelKCB-4C15
Cores4
Conductor size1.5 mm²
InsulationPVC
Voltage rating300/500 V
Length per coil100 m
Core coloursColour-coded cores

Where it fits

  • Indoor-to-outdoor interconnecting cable on small split systems
  • Control wiring for valves, actuators and fan coil units
  • Three-phase control and signal circuits at low current
  • Power for small three-phase fans and pumps over short runs

Fitting and checking

Follow the terminal markings of the manufacturer so that live, neutral, earth and signal cores meet the right terminals; reversed conductors are a common cause of communication errors and blown boards. Keep signal cores away from heavy power cables where the manual says to, and make sure the cable length does not exceed the maximum interconnect length given for the model.

Compared with the other cables

Across the 6 models in Klima Cables (3 & 4 Core), the values that vary are cores and conductor size. Every model in the family has the same insulation (PVC), voltage rating (300/500 V), length per coil (100 m) and core colours (Colour-coded cores), so the choice comes down to the values above.

SpecificationThis modelAcross the range
Cores43 to 4
Conductor size1.5 mm²1.5 to 4 mm²

This is the smallest model in the range by conductor size. The next step up is Klima 4-Core Flexible Cable 2.5 mm² (2.5 mm²). Quote the model code KCB-4C15 when you enquire so that the right size is supplied.

Questions

Why do some split systems need four cores between the units?

Three cores carry live, neutral and earth. The fourth carries the communication or control signal between the indoor and outdoor boards, so the indoor unit can start and stop the outdoor one.

Can I join two lengths of cable to reach the outdoor unit?

Avoid joints in interconnect cable where possible. If a joint is unavoidable, use a proper connector box that is insulated, supported and accessible, and follow the local regulations.

Selection, care and fault-finding notes for the whole family are on the Klima Cables (3 & 4 Core) page, and the contact page takes enquiries with the model code KCB-4C15.