Klima 4-Core Flexible Cable 4 mm²
4-core flexible copper cable, 4 mm² per core, PVC insulated, for air conditioner interconnecting and power wiring.
Klima Cables (3 & 4 Core) · Model KCB-4C4
About this cable
The 4 mm² four-core cable is the heaviest in the range. It carries three phases and earth to larger three-phase compressors and packaged units, and to long runs where voltage drop would be a problem at a smaller size. The copper conductors have PVC insulation and sheath rated 300/500 V, supplied in 100 m coils with colour-coded cores.
The larger conductor keeps the drop low, around 9.5 mV per ampere per metre for three-phase circuits, so a 25 A load 40 m from the board loses about 9.5 × 25 × 40 ÷ 1000 = 9.5 V of a 400 V supply, about 2.4 %. The same run in 2.5 mm² would lose about 15 V (3.8 %), and the extra heat would shorten the cable's life when it is bundled with other circuits.
Specifications
| Specification | Value |
|---|---|
| Model | KCB-4C4 |
| Cores | 4 |
| Conductor size | 4 mm² |
| Insulation | PVC |
| Voltage rating | 300/500 V |
| Length per coil | 100 m |
| Core colours | Colour-coded cores |
Where it fits
- Three-phase supply to larger compressors and packaged rooftop units
- Long runs between a main board and remote condensing units
- Feeders to plant-room sub-panels and pump sets
- Replacement for cable that has run warm or dropped too much voltage
Fitting and checking
Check the capacity of the cable under your installation method, since bundling and warm ambient temperatures lower the current it can carry. Terminate with lugs or ferrules suited to a 4 mm² conductor, torque the screws to the specified value and check them again after the first weeks of running. Mark the cable at both ends so that the phase sequence is clear at every future service.
Compared with the other cables
The 6 models in Klima Cables (3 & 4 Core) differ mainly in cores and conductor size. Every model in the family has the same insulation (PVC), voltage rating (300/500 V), length per coil (100 m) and core colours (Colour-coded cores), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Cores | 4 | 3 to 4 |
| Conductor size | 4 mm² | 1.5 to 4 mm² |
This is the largest model in the range by conductor size. The next step down is Klima 4-Core Flexible Cable 2.5 mm² (2.5 mm²). Quote the model code KCB-4C4 when you enquire so that the right size is supplied.
Questions
Can I terminate 4 mm² cable on any contactor?
Check the terminal capacity in the contactor's datasheet. Most contactors in this range accept 4 mm², and a ferrule keeps stranded conductors tidy.
Why does cable get warm in service?
Current heats any conductor. A warm cable that is bundled, coiled or in a hot space may be carrying more than its installed rating allows, which is a reason to move up a size or change the route.
Selection, care and fault-finding notes for the whole family are on the Klima Cables (3 & 4 Core) page, and the contact page takes enquiries with the model code KCB-4C4.