Klima Industries

Klima Filter Drier 1/4 in Flare

Liquid line filter drier with 1/4 in flare connections.

Klima Filter Driers · Model KFD-L14F

About this filter drier

This is the smallest filter drier in the range: a liquid-line drier with 1/4 in flare connections and a molecular sieve desiccant, for R22, R134a, R404A, R407C and R410A. A sealed drier is fitted ahead of the expansion device to remove moisture and filter out particles, and flare ends mean it goes into a small line without brazing, which helps where a torch is hard to use, such as in occupied rooms.

A drier does not last indefinitely: its desiccant is saturated by the moisture it captures. On a system that has been opened, fit a new drier before evacuating, and keep the drier sealed until the last moment, because the desiccant takes up moisture from the air. R32 is not in the list of refrigerants for this model, so check the datasheet before using it with other refrigerants.

Specifications

SpecificationValue
ModelKFD-L14F
TypeLiquid line
Connection size1/4 in
Connection styleFlare
DesiccantMolecular sieve
RefrigerantsR22, R134a, R404A, R407C, R410A

Where it fits

  • Liquid line of small split systems with 1/4 in flare connections
  • Small refrigeration systems such as bottle coolers and display cabinets
  • Replacement after a leak repair or a compressor change
  • Installations where brazing near the drier is not practical

Fitting and checking

Fit the drier with the flow arrow pointing towards the expansion device, and flare each pipe end carefully: a poor flare is the commonest cause of leaks at this size. Smear a little refrigeration oil on the flare face, and tighten to about the torque in the equipment manual, often near 15 N·m for 1/4 in. Leak test with nitrogen and evacuate before opening the service valves.

Compared with the other filter driers

The 6 models in Klima Filter Driers differ mainly in type, connection size and connection style. Every model in the family has the same desiccant (Molecular sieve) and refrigerants (R22, R134a, R404A, R407C, R410A), so the choice comes down to the values above.

SpecificationThis modelAcross the range
TypeLiquid lineLiquid line / Bi-flow / Suction line
Connection size1/4 in0.25 to 0.625 in
Connection styleFlareFlare / Solder

This is the smallest model in the range by connection size. The next step up is Klima Filter Drier 3/8 in Flare (3/8 in). Quote the model code KFD-L14F when you enquire so that the right size is supplied.

Questions

Should I replace the drier every time I open the system?

Yes, whenever the circuit is open to air. A drier that has already taken up its load of moisture cannot protect a system that has just been exposed.

Can I braze a flare drier into the line instead?

No. Flare ends are designed for flare nuts, not for heat. Use the solder-connection driers where a brazed joint is required.

Selection, care and fault-finding notes for the whole family are on the Klima Filter Driers page, and the contact page takes enquiries with the model code KFD-L14F. For background reading, see the guide Filter driers and drier cores: when to fit and how to choose.