How to choose a run capacitor for an air conditioner
Match capacitance, voltage and terminals to the nameplate, and learn how to tell when a capacitor has weakened.
Related products
What a run capacitor does
The compressor and condenser fan in most single-phase air conditioners are induction motors with a main winding and an auxiliary winding. A run capacitor sits in series with the auxiliary winding and shifts its current ahead of the main winding, which creates the rotating field the motor needs to start and to run efficiently. When the capacitor weakens, the motor draws more current, runs hotter and eventually stalls.
A dual run capacitor puts two capacitors in one can: one for the compressor, marked HERM, and one for the fan, marked FAN, with a shared common terminal marked C.
Three values to match
- Capacitance in µF. Copy the value printed on the old part. The tolerance is usually ±5 %. A dual capacitor shows two numbers, such as 35 + 5 µF.
- Rated voltage in V AC. Choose the same or higher. The common classes are 370 V and 440 V. A lower voltage than the original fails early.
- Case and terminals. Check diameter, height, bracket style and whether the terminals are fast-on or screw type, so the part fits the space and the wiring.
Run capacitors and start capacitors are different parts
A run capacitor stays in the circuit while the motor runs, so it is built for continuous duty and is rated at 370 V or 440 V. A start capacitor is in the circuit for only a second or two while the motor accelerates. It has a much higher capacitance, a lower voltage rating and is switched out by a relay or a PTC device. Never fit a start capacitor where the unit calls for a run capacitor, or the reverse, because each is built for a different duty.
Voltage rating and temperature rating
The rated voltage is not the supply voltage. In a permanent split capacitor motor the voltage across the capacitor can be higher than the supply, which is why a 230 V unit normally uses a 370 V or 440 V part. A capacitor of the same capacitance with a higher voltage rating is a safe replacement and often lasts longer in hot conditions. A lower rating is not.
Check the temperature rating as well. Many run capacitors are rated for a maximum case temperature of 70 °C, and some for 85 °C. The outdoor unit of an air conditioner can stand in direct sun, and that heat can decide whether a capacitor lasts several seasons or fails in one.
Reading a dual capacitor label
A label that reads 35 + 5 µF 440 V means 35 µF between C and HERM for the compressor and 5 µF between C and FAN for the fan motor, rated at 440 V AC. Photograph the wiring before you disconnect anything, then move each wire to the same marked terminal on the new part, one at a time.
How to replace a capacitor safely
- Switch off the supply at the isolator and confirm with a meter that the unit is dead.
- Discharge the old capacitor through an insulated resistor across its terminals, then check that no voltage remains. Do not short the terminals with a screwdriver.
- Photograph the wiring and note which wire goes to C, HERM and FAN.
- Measure the old capacitor if you can, so that you know whether it was the fault.
- Fit the new capacitor in the same bracket and position, and tighten the strap so that it cannot vibrate.
- Move the wires one at a time to the matching terminals. Replace any terminal that is loose, discoloured or burnt; a terminal crimp fitted with the right tool gives a firm joint.
- Restore power, run the unit and compare the motor currents with the nameplate.
Test before you replace
- Switch off the supply and discharge the capacitor through an insulated resistor.
- Use a meter with a capacitance range and measure each section: C to HERM, and C to FAN.
- Replace the capacitor if a reading is outside the tolerance printed on the label, or about 10 % or more below the rated value.
Signs that a capacitor is failing
- A swollen top, a bulging case or oil leaking from the can
- A compressor that hums but does not start, or a fan that needs a push to turn
- High running current, repeated overload trips or a unit that shuts down on hot afternoons
Heat shortens capacitor life
Capacitors age faster in high ambient temperatures, and the outdoor unit of an air conditioner is often in direct sun. In hot climates choose a rated voltage with margin, and check capacitance during every service visit before the peak cooling season rather than waiting for a failure.
If the new capacitor fails again
A capacitor that fails soon after replacement is a symptom, and the cause is usually one of these:
- A wrong rating: a capacitance far from the original, or a voltage class that is too low
- A loose or burnt terminal that overheats the connection
- A motor with shorted windings or a worn bearing that draws too much current
- A high supply voltage or repeated surges
- A hot control box or direct sun on the capacitor
Questions about run capacitors
Can I use a capacitor with a higher µF value?
Use the value on the original label. A higher value raises the winding current and heat, and a lower value cuts torque and efficiency. If you cannot find the exact value, ask the equipment maker, and stay within the tolerance printed on the old part.
Can a dual run capacitor replace two single capacitors?
Yes, provided each capacitance matches, the voltage rating is the same or higher and the common terminal is wired correctly. Keep two single capacitors if you cannot find a dual with the same pair of values.
How long does a run capacitor last?
There is no fixed life. Heat, running hours and voltage spikes decide it. Capacitors in outdoor units in hot climates often weaken within a few years, so test the capacitance at every service.
Can I test a capacitor without a capacitance meter?
A multimeter without a capacitance range can show that a capacitor is shorted or open, but not that it has weakened, and a weak capacitor is the most common fault. Use a meter with a capacitance range.