Contactor sizing for compressors: poles, current and coil voltage

How to pick a contactor for a compressor or fan: pole count, motor-duty current rating and coil voltage explained.

Related products

What a contactor does

A contactor is an electrically operated switch. The thermostat or controller energises a small coil, and the main contacts close to feed full line current to the compressor or condenser fan. Because the contacts make and break high currents hundreds of times a day, they wear, and pitted contacts are one of the commonest causes of intermittent cooling faults.

Poles

  • A 1-pole contactor breaks one line, which is common on small single-phase condensing units.
  • A 2-pole contactor breaks both lines of a single-phase supply.
  • A 3-pole contactor breaks all three phases of a three-phase compressor.

Current rating

Size the contactor from the compressor nameplate, which lists the rated load amps (RLA) and the locked rotor amps (LRA). The contactor must carry the running current continuously and make and break the starting current without welding. Choose a rated operational current for motor duty, shown as utilisation category AC-3, that is comfortably above the RLA. A rating for resistive duty, AC-1, is higher for the same body and does not describe a motor load.

Allow extra margin where the control box is hot, because contactors derate at high ambient temperatures, and where the compressor starts often.

A worked example

Take a three-phase scroll compressor on a 400 V supply with a nameplate that shows RLA 22 A and LRA 130 A. A 3-pole contactor with an AC-3 rating of 25 A would carry the running current on paper, but with only about 14 % of margin it leaves little room for a hot control box. A 32 A AC-3 contactor gives a comfortable margin. Contactors built to the IEC standard for motor duty can make about eight to ten times their rated current, so 130 A of locked rotor current is well inside what a 32 A contactor is designed to switch.

In North America and some other markets, definite-purpose contactors for air conditioning are rated directly in full-load amps (FLA) and locked-rotor amps (LRA). Compare those two figures with the compressor RLA and LRA in the same way.

Utilisation categories at a glance

CategoryTypical loadUse for compressors?
AC-1Resistive loads such as heatersNo. The rating is higher for the same body, but it does not cover motor starting.
AC-3Squirrel-cage motors, switched off while runningYes. Size compressors and condenser fans from this rating.
AC-4Plugging and inching dutyRarely needed in cooling equipment.

Coil voltage

The coil voltage must match the control circuit that energises it. Thermostat circuits in most air conditioners are 24 V AC, supplied by a control transformer. Others use 110/120 V or 220/240 V. A coil on the wrong voltage either fails to pull in or burns out.

Coil voltage tolerance and control wiring

A contactor coil is designed to pull in reliably between about 85 % and 110 % of its rated voltage. A 24 V coil that sees only 19 V, because of a long run of thin cable or an overloaded transformer, can chatter, run hot and wear the contacts. Measure the coil voltage while the contactor is pulling in, not with the load switched off.

A larger contactor also has a larger coil. A small control transformer that coped with the old coil can be overloaded by a bigger one, so check the transformer rating in volt-amperes before you upsize.

Why contactors fail

  • Pitted, blackened or welded contacts from repeated switching under load
  • Low coil voltage that makes the contactor chatter and buzz
  • Rapid restarts that stress the contacts and the compressor; a delay on make timer prevents them
  • Insects, dust and moisture in the control box

Replacing a contactor

  1. Isolate the supply and prove that the circuit is dead.
  2. Photograph the wiring and label the wires. The line side is marked L1, L2 and L3, the load side T1, T2 and T3, and the coil terminals A1 and A2.
  3. Fit the new contactor on the same rail or plate and connect each wire to the same marked terminal.
  4. Tighten every terminal to the torque printed on the contactor. A loose lug becomes a hot spot.
  5. Replace damaged or discoloured wire ends instead of reusing them.
  6. Power up, let the contactor pull in a few times and listen for chatter. Measure the compressor current and compare it with the nameplate.

Protect the compressor from short cycling

A compressor should not restart until the pressures across it have equalised. Restarting against a high head pressure overloads the motor and the contactor. A delay on make timer in the control circuit holds the contactor off for a set time after a stop or after power returns, and compressor makers commonly specify a minimum off time of three minutes or more.

Quick checklist

  1. Read RLA and LRA from the compressor nameplate.
  2. Choose the pole count for the supply: 2-pole single-phase, 3-pole three-phase.
  3. Choose an AC-3 current rating above the RLA, with margin for heat.
  4. Match the coil voltage to the control circuit.
  5. Check dimensions and mounting before you order.

Questions about contactors

Does a contactor protect the compressor from overload?

No. A contactor only makes and breaks the circuit. Overload protection comes from the compressor’s internal protector, a thermal overload relay or a motor protection device in the same circuit.

Can I fit a bigger contactor than the original?

Yes, if the coil voltage and mounting match. A larger contactor has more margin on its contacts, but its coil draws more current, so check that the control transformer can supply it.

How do I tell that a contactor is worn out?

Look for blackened, pitted or welded contacts, a burnt smell, a loud hum from the coil and a measurable voltage drop across the closed contacts while the load runs. Replace the contactor instead of filing the contacts.