Klima 3-Pole Contactor 25 A, 24 V Coil
3-pole contactor rated 25 A with a 24 V AC coil for compressor and fan switching.
Klima Contactors ยท Model KCT-3P25-24
About this contactor
Three poles mean this contactor can disconnect all three phases of a three-phase motor, which is why it is the normal choice for three-phase compressors and fan motors in small packaged and split systems. It is rated 25 A with a 24 V AC coil and mounts on a screw plate or DIN rail. The 24 V coil lets the control transformer and a low-voltage thermostat operate it safely.
A contactor does not protect a motor from overload, so it is normally fitted with an overload relay or a motor protector, and scroll compressors also need a phase-failure and phase-sequence relay because they are damaged by running backwards. For sizing, compare the compressor's rated load current and locked-rotor current with the contactor rating and utilisation category in the datasheet, rather than with the compressor's horsepower.
Specifications
| Specification | Value |
|---|---|
| Model | KCT-3P25-24 |
| Poles | 3 |
| Rated current | 25 A |
| Coil voltage | 24 V AC |
| Frequency | 50/60 Hz |
| Mounting | Screw or DIN rail |
Where it fits
- Three-phase compressors in small packaged and condensing units
- Condenser fan motors and pump motors on three-phase supplies
- Replacement for a worn 24 V three-pole contactor in rooftop units
- Panels that use a 24 V transformer to control several contactors
Fitting and checking
Mark the three load wires before removal and fit them to the same terminals; swapping two phases reverses the rotation of a scroll compressor, which can destroy it in minutes. After fitting, check the three phase voltages and the running current of each phase; a large imbalance indicates a loose terminal, a worn contact or a supply problem rather than a faulty contactor.
Compared with the other contactors
The 7 models in Klima Contactors differ mainly in poles, rated current and coil voltage. Every model in the family has the same frequency (50/60 Hz) and mounting (Screw or DIN rail), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Poles | 3 | 2 to 3 |
| Rated current | 25 A | 25 to 63 A |
| Coil voltage | 24 V AC | 24 V AC / 230 V AC |
This is the smallest model in the range by rated current. The next step up is Klima 3-Pole Contactor 32 A, 24 V Coil (32 A). Quote the model code KCT-3P25-24 when you enquire so that the right size is supplied.
Questions
Is a 25 A contactor enough for my compressor?
Compare it with the compressor's rated load current and locked-rotor current on the nameplate, and confirm the utilisation category in the datasheet. If the current is close to the limit, go to the 32 A or 40 A model.
Do I still need an overload relay?
Yes. The contactor only switches the current. A separate overload device, or a motor protector built into the compressor, protects the motor.
Selection, care and fault-finding notes for the whole family are on the Klima Contactors page, and the contact page takes enquiries with the model code KCT-3P25-24. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.