Klima Delay on Make Timer, Adjustable, 24 V AC/DC
Adjustable delay on make timer on 24 V AC/DC; holds the compressor off for 0.1 to 10 min after power or a thermostat call.
Klima Delay on Make Timer ยท Model KDM-24A
About this delay on make timer
Where one fixed delay does not fit every job, this adjustable timer covers 0.1 to 10 minutes on a 24 V AC or DC supply, with a 5 A contact and a plug-in or surface mount. The same unit can set a three-minute hold-off for a compressor, stagger the start of several loads at ten-second steps, or delay a fan start after a heater stage. The low-voltage supply suits systems with a 24 V transformer and DC control circuits.
Setting the delay is a design decision, not a guess. For compressor protection, use the manufacturer's minimum off time, normally about three minutes. For staging, work out the sequence so that the largest load starts first or last, according to the plant. During commissioning a short delay helps testing, but return it to the working value before you leave the site.
Specifications
| Specification | Value |
|---|---|
| Model | KDM-24A |
| Supply voltage | 24 V AC/DC |
| Delay range | 0.1 to 10 min |
| Contact rating | 5 A |
| Mounting | Plug-in / surface |
Where it fits
- Sequential starting of several compressors or fan groups on one supply
- Fan start delay after a heater or cooling stage on a 24 V control circuit
- Compressor protection where the maker's minimum off time is not three minutes
- Test benches and commissioning where the delay must be adjusted
Fitting and checking
Wire the supply to the 24 V circuit and the output in series with the load's contactor coil. Turn the dial to the required time and check it with a stopwatch: a dial scale is a guide and the actual time should be confirmed. Mark the final setting on the panel label, so that the next technician does not change it by accident.
Compared with the other delay on make timers
This model is one of 4 in Klima Delay on Make Timer; what changes from one to the next is supply voltage and delay range. Every model in the family has the same contact rating (5 A) and mounting (Plug-in / surface), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Supply voltage | 24 V AC/DC | 24 V AC/DC / 230 V AC |
| Delay range | 0.1 to 10 min | 3 min fixed / 0.1 to 10 min |
The closest alternative in the range is Klima Delay on Make Timer, Fixed, 24 V AC/DC, which shares 3 of the 4 listed specifications and differs in delay range. Quote the model code KDM-24A when you enquire.
Questions
What does a range of 0.1 to 10 minutes allow?
It lets the same part be used for short delays, such as 6 seconds for relay sequencing, and long ones, such as 5 or 10 minutes for compressor protection or staged start-up.
Can several of these timers share one transformer?
Yes, if the transformer's VA covers all the timers, contactor coils and other control loads, including the higher pull-in values.
Selection, care and fault-finding notes for the whole family are on the Klima Delay on Make Timer page, and the contact page takes enquiries with the model code KDM-24A. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.