Klima Industries

Klima Delay on Make Timer, Fixed, 24 V AC/DC

Fixed delay on make timer on 24 V AC/DC; holds the compressor off for 3 min fixed after power or a thermostat call.

Klima Delay on Make Timer ยท Model KDM-24F

About this delay on make timer

A delay on make timer waits a set time after power is applied before closing its output. This model has a fixed 3-minute delay, a 24 V AC or DC supply and a 5 A contact, and it plugs into a base or mounts on a surface. The main use is compressor protection: after a power cut, or after the thermostat has just switched the compressor off, a three-minute wait lets the high and low pressures equalise so the compressor does not have to start against the head pressure of the system.

The 24 V supply makes it the natural match for packaged units, heat pumps and fan coil controls that already have a 24 V transformer. The AC/DC rating means it also suits low-voltage DC control circuits. The contact is for control duty: let it switch a contactor coil or a relay, and let the contactor switch the compressor.

Specifications

SpecificationValue
ModelKDM-24F
Supply voltage24 V AC/DC
Delay range3 min fixed
Contact rating5 A
MountingPlug-in / surface

Where it fits

  • Anti-short-cycle protection for compressors on 24 V control circuits
  • Packaged and split units that restart when a power cut ends
  • Heat pumps and rooftop units with a low-voltage thermostat
  • Any 24 V circuit that needs a three-minute hold-off before a load starts

Fitting and checking

Wire the supply terminals across the 24 V circuit and put the output contact in series with the contactor coil, so that the coil is energised only after the delay. Test by switching the supply off and on and timing the delay with a watch; it should be close to three minutes. If a transformer powers many loads, check that it can supply the timer as well as the coils.

Compared with the other delay on make timers

Across the 4 models in Klima Delay on Make Timer, the values that vary are supply voltage and delay range. Every model in the family has the same contact rating (5 A) and mounting (Plug-in / surface), so the choice comes down to the values above.

SpecificationThis modelAcross the range
Supply voltage24 V AC/DC24 V AC/DC / 230 V AC
Delay range3 min fixed3 min fixed / 0.1 to 10 min

The closest alternative in the range is Klima Delay on Make Timer, Fixed, 230 V AC, which shares 3 of the 4 listed specifications and differs in supply voltage. Quote the model code KDM-24F when you enquire.

Questions

Why does a compressor need a delay before restarting?

Right after it stops, the pressure on the discharge side is still high. Starting against that pressure overloads the motor and wears the compressor, so waiting a few minutes allows the pressures to equalise.

Can this timer switch the compressor directly?

No. Its 5 A contact is meant for a contactor coil or a small relay. Let the contactor carry the compressor current.

Selection, care and fault-finding notes for the whole family are on the Klima Delay on Make Timer page, and the contact page takes enquiries with the model code KDM-24F. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.