Klima Delay on Make Timer, Fixed, 230 V AC

Fixed delay on make timer on 230 V AC; holds the compressor off for 3 min fixed after power or a thermostat call.

Klima Delay on Make Timer ยท Model KDM-230F

About this delay on make timer

This delay on make timer has the same fixed 3-minute delay but runs from a 230 V AC supply, so it suits mains-voltage control circuits with no transformer: cold-room controllers, packaged units with line-voltage thermostats and simple panels for condensing units. It carries a 5 A contact and fits a plug-in base or a surface mount.

On a site with many units, a fixed delay has a drawback. If a power cut ends and several units each wait exactly three minutes, they all restart at the same moment and the combined starting current can trip the supply again. In that case give the units different delays, using the adjustable model, or let each unit see its own power-restore sequence. For a single unit, three minutes is the usual protection.

Specifications

SpecificationValue
ModelKDM-230F
Supply voltage230 V AC
Delay range3 min fixed
Contact rating5 A
MountingPlug-in / surface

Where it fits

  • Cold-room and display-cabinet condensing units with a 230 V control circuit
  • Packaged and split systems that use a line-voltage thermostat
  • Control panels without a 24 V transformer
  • Replacement for a failed 230 V time delay relay of fixed value

Fitting and checking

Isolate the supply and wire the timer's supply terminals to the control circuit, with the output contact in series with the contactor coil. Because the circuit is at mains voltage, the wiring needs the same insulation and segregation as the power wiring. Test by removing and restoring power: the load should start only after the delay.

Compared with the other delay on make timers

This model is one of 4 in Klima Delay on Make Timer; what changes from one to the next is supply voltage and delay range. Every model in the family has the same contact rating (5 A) and mounting (Plug-in / surface), so the choice comes down to the values above.

SpecificationThis modelAcross the range
Supply voltage230 V AC24 V AC/DC / 230 V AC
Delay range3 min fixed3 min fixed / 0.1 to 10 min

The closest alternative in the range is Klima Delay on Make Timer, Fixed, 24 V AC/DC, which shares 3 of the 4 listed specifications and differs in supply voltage. Quote the model code KDM-230F when you enquire.

Questions

Why is the output delayed and not the input?

The timer starts counting when power is applied and closes its contact when the time is up. This holds off the compressor contactor for a set time after every restoration of power.

Is a 5 A contact enough for a coil?

Yes. A contactor coil draws a small fraction of an ampere at holding and somewhat more at pull-in, well within a 5 A contact.

Selection, care and fault-finding notes for the whole family are on the Klima Delay on Make Timer page, and the contact page takes enquiries with the model code KDM-230F. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.