Klima HVAC Transformer 230 V to 24 V, 40 VA
Control transformer, 230 V primary, 24 V AC secondary, 40 VA.
Klima Transformer for HVAC · Model KTF-230-40
About this transformer
The KTF-230-40 steps a 230 V supply down to 24 V AC for control circuits, at a rating of 40 VA. At 24 V that is 1.67 A on the secondary; on the primary the same 40 VA draws about 0.17 A at 230 V. It is rated for 50 and 60 Hz, mounts on a plate and carries a thermal cut-out.
The rating is a budget, and sizing is addition. Add up the VA of every load on the 24 V circuit (contactor coils, valves, relays and the thermostat) and choose a transformer at least 20 % above the total. For this model that means the loads should not add up to more than about 33 VA (40 ÷ 1.2). Count the pull-in VA of coils, which is higher than their holding VA, when several of them energise at once. If your total gets close to 33 VA, step up to the 75 VA model.
Specifications
| Specification | Value |
|---|---|
| Model | KTF-230-40 |
| Primary voltage | 230 V |
| Secondary voltage | 24 V AC |
| Rating | 40 VA |
| Frequency | 50/60 Hz |
| Mounting | Plate |
| Protection | Thermal cut-out |
Where it fits
- 24 V AC control circuits on split, packaged and fan coil equipment
- Supplying thermostats, relays and valve actuators from a 230 V supply
- Replacing a burnt control transformer on a 230 V supply
- Panels where a 40 VA plate-mounted unit suits the layout
Fitting and checking
Isolate and lock off the supply. Fix the transformer to the plate, connect the 230 V primary through a fuse or breaker as the panel design requires and connect the 24 V AC secondary to the control circuit. Measure the secondary with the load connected: an unloaded transformer reads somewhat above its rated voltage, so a reading taken with nothing connected can mislead. If the thermal cut-out has operated, find the overload before you replace anything.
Compared with the other HVAC transformers
Across the 4 models in Klima Transformer for HVAC, the values that vary are primary voltage and rating. Every model in the family has the same secondary voltage (24 V AC), frequency (50/60 Hz), mounting (Plate) and protection (Thermal cut-out), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Primary voltage | 230 V | 230 V / 110/120 V / 380/400 V |
| Rating | 40 VA | 40 to 100 VA |
This is the smallest model in the range by rating. The next step up is Klima HVAC Transformer 230 V to 24 V, 75 VA (75 VA). Quote the model code KTF-230-40 when you enquire so that the right size is supplied.
Questions
What does the thermal cut-out do?
It opens when the winding overheats, which protects the transformer from an overload. It does not replace a fuse or breaker where the panel design calls for one.
How do I know 40 VA is enough?
Add the VA of every 24 V load and multiply by 1.2. If the result is 40 VA or less, this model is enough; if not, use the 75 VA model.
Selection, care and fault-finding notes for the whole family are on the Klima Transformer for HVAC page, and the contact page takes enquiries with the model code KTF-230-40. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.