Klima HVAC Transformer 230 V to 24 V, 40 VA

Control transformer, 230 V primary, 24 V AC secondary, 40 VA.

Klima Transformer for HVAC · Model KTF-230-40

About this transformer

The KTF-230-40 steps a 230 V supply down to 24 V AC for control circuits, at a rating of 40 VA. At 24 V that is 1.67 A on the secondary; on the primary the same 40 VA draws about 0.17 A at 230 V. It is rated for 50 and 60 Hz, mounts on a plate and carries a thermal cut-out.

The rating is a budget, and sizing is addition. Add up the VA of every load on the 24 V circuit (contactor coils, valves, relays and the thermostat) and choose a transformer at least 20 % above the total. For this model that means the loads should not add up to more than about 33 VA (40 ÷ 1.2). Count the pull-in VA of coils, which is higher than their holding VA, when several of them energise at once. If your total gets close to 33 VA, step up to the 75 VA model.

Specifications

SpecificationValue
ModelKTF-230-40
Primary voltage230 V
Secondary voltage24 V AC
Rating40 VA
Frequency50/60 Hz
MountingPlate
ProtectionThermal cut-out

Where it fits

  • 24 V AC control circuits on split, packaged and fan coil equipment
  • Supplying thermostats, relays and valve actuators from a 230 V supply
  • Replacing a burnt control transformer on a 230 V supply
  • Panels where a 40 VA plate-mounted unit suits the layout

Fitting and checking

Isolate and lock off the supply. Fix the transformer to the plate, connect the 230 V primary through a fuse or breaker as the panel design requires and connect the 24 V AC secondary to the control circuit. Measure the secondary with the load connected: an unloaded transformer reads somewhat above its rated voltage, so a reading taken with nothing connected can mislead. If the thermal cut-out has operated, find the overload before you replace anything.

Compared with the other HVAC transformers

Across the 4 models in Klima Transformer for HVAC, the values that vary are primary voltage and rating. Every model in the family has the same secondary voltage (24 V AC), frequency (50/60 Hz), mounting (Plate) and protection (Thermal cut-out), so the choice comes down to the values above.

SpecificationThis modelAcross the range
Primary voltage230 V230 V / 110/120 V / 380/400 V
Rating40 VA40 to 100 VA

This is the smallest model in the range by rating. The next step up is Klima HVAC Transformer 230 V to 24 V, 75 VA (75 VA). Quote the model code KTF-230-40 when you enquire so that the right size is supplied.

Questions

What does the thermal cut-out do?

It opens when the winding overheats, which protects the transformer from an overload. It does not replace a fuse or breaker where the panel design calls for one.

How do I know 40 VA is enough?

Add the VA of every 24 V load and multiply by 1.2. If the result is 40 VA or less, this model is enough; if not, use the 75 VA model.

Selection, care and fault-finding notes for the whole family are on the Klima Transformer for HVAC page, and the contact page takes enquiries with the model code KTF-230-40. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.