Klima HVAC Transformer 230 V to 24 V, 75 VA
Control transformer, 230 V primary, 24 V AC secondary, 75 VA.
Klima Transformer for HVAC · Model KTF-230-75
About this transformer
The KTF-230-75 is the 75 VA step in the range: 230 V primary, 24 V AC secondary, 50/60 Hz, plate mounting and a thermal cut-out. At 24 V it can deliver 3.13 A, nearly double the 1.67 A of the 40 VA model, and on the primary it draws about 0.33 A at 230 V. With the usual 20 % margin, loads of up to about 62 VA (75 ÷ 1.2) are within its rating.
That headroom is what panels with several things on the 24 V circuit need: contactor coils, valve actuators, relays and a thermostat all drawing together. The deciding number is pull-in VA, because coils draw more while they close than while they hold, and several can close at the same moment after a power cut. If the 24 V side keeps dropping out when the compressor starts, the transformer may be too small. More VA also means a larger and warmer unit, so mount it where air can circulate and keep it clear of heat from other components.
Specifications
| Specification | Value |
|---|---|
| Model | KTF-230-75 |
| Primary voltage | 230 V |
| Secondary voltage | 24 V AC |
| Rating | 75 VA |
| Frequency | 50/60 Hz |
| Mounting | Plate |
| Protection | Thermal cut-out |
Where it fits
- Panels with several contactor coils, valves and relays on one 24 V circuit
- Multi-zone and multi-unit control panels on a 230 V supply
- Upgrading where a 40 VA transformer is overloaded or runs hot
- Replacing a failed 75 VA plate-mounted transformer
Fitting and checking
Isolate the supply and fix the transformer to the plate with space around it. Connect the 230 V primary through a fuse or breaker as the panel design requires, wire the secondary to the control circuit with cable sized for the current and measure the secondary voltage with the load running. A thermal cut-out that opens repeatedly points to a load that is too big or a short on the 24 V side, so look for that before you swap the transformer.
Compared with the other HVAC transformers
This model is one of 4 in Klima Transformer for HVAC; what changes from one to the next is primary voltage and rating. Every model in the family has the same secondary voltage (24 V AC), frequency (50/60 Hz), mounting (Plate) and protection (Thermal cut-out), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Primary voltage | 230 V | 230 V / 110/120 V / 380/400 V |
| Rating | 75 VA | 40 to 100 VA |
Ordered by rating, this model is number 3 of 4: the next step down is Klima HVAC Transformer 230 V to 24 V, 40 VA (40 VA) and the next step up is Klima HVAC Transformer 400 V to 24 V, 100 VA (100 VA). Quote the model code KTF-230-75 when you enquire so that the right size is supplied.
Questions
Should I choose 40 VA or 75 VA?
Add the VA of every 24 V load and multiply by 1.2. If loads total 45 VA the rule gives 54 VA, which is more than the 40 VA model can supply, so the 75 VA model is the right choice.
Can I run two transformers in parallel to get more VA?
Do not join secondaries in parallel unless the maker says it is permitted: unequal impedances make them share the load unevenly, and wrong polarity causes a short circuit. Fit one transformer of the right size.
Selection, care and fault-finding notes for the whole family are on the Klima Transformer for HVAC page, and the contact page takes enquiries with the model code KTF-230-75. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.