Klima HVAC Transformer 400 V to 24 V, 100 VA
Control transformer, 380/400 V primary, 24 V AC secondary, 100 VA.
Klima Transformer for HVAC · Model KTF-400-100
About this transformer
The KTF-400-100 is the largest control transformer in the range: a 380/400 V primary, a 24 V AC secondary and 100 VA, rated for 50 and 60 Hz, with plate mounting and a thermal cut-out. The secondary can deliver 4.17 A at 24 V, and the primary draws about 0.26 A at 380 V and 0.25 A at 400 V. It is made for three-phase equipment, where the control supply is taken between two phases of a 380/400 V supply.
That connection is the detail to get right. The primary is rated for the voltage between two phases. Connected between a phase and neutral, which is about 230 V, the 24 to 400 ratio would give a secondary of roughly 14 V, too low to pull in 24 V coils. The sizing rule is the same as for the smaller models: loads of up to about 83 VA (100 ÷ 1.2) fit within a 20 % margin, and above that the circuit needs a larger transformer or a second 24 V supply.
Specifications
| Specification | Value |
|---|---|
| Model | KTF-400-100 |
| Primary voltage | 380/400 V |
| Secondary voltage | 24 V AC |
| Rating | 100 VA |
| Frequency | 50/60 Hz |
| Mounting | Plate |
| Protection | Thermal cut-out |
Where it fits
- Three-phase chillers and packaged units with a 24 V control circuit
- Compressor racks with several contactors and solenoid valves
- Panels that take control power between two phases of a 380/400 V supply
- Replacing a transformer that failed from a heavy 24 V load
Fitting and checking
Measure the supply between the two conductors the primary will connect to and confirm it is 380 to 400 V, not 230 V. Cover or shroud the primary terminals, since they carry the full line voltage, connect through a fuse or breaker chosen under the panel rules and fix the transformer to the plate. Measure the secondary with the load running. A thermal cut-out that opens points to an overload or a short on the 24 V side.
Compared with the other HVAC transformers
Across the 4 models in Klima Transformer for HVAC, the values that vary are primary voltage and rating. Every model in the family has the same secondary voltage (24 V AC), frequency (50/60 Hz), mounting (Plate) and protection (Thermal cut-out), so the choice comes down to the values above.
| Specification | This model | Across the range |
|---|---|---|
| Primary voltage | 380/400 V | 230 V / 110/120 V / 380/400 V |
| Rating | 100 VA | 40 to 100 VA |
This is the largest model in the range by rating. The next step down is Klima HVAC Transformer 230 V to 24 V, 75 VA (75 VA). Quote the model code KTF-400-100 when you enquire so that the right size is supplied.
Questions
Can this transformer be connected between a phase and neutral?
No. Its primary is for 380/400 V, the voltage between two phases. On a 230 V phase-to-neutral supply the secondary would be about 14 V, too low for 24 V coils.
How do I choose between this and the 230 V models?
By supply voltage first. This model has a 380/400 V primary, and the 230 V models cannot be connected to that supply. Then add up your 24 V loads and multiply by 1.2: up to about 83 VA fits this model.
Selection, care and fault-finding notes for the whole family are on the Klima Transformer for HVAC page, and the contact page takes enquiries with the model code KTF-400-100. For background reading, see the guide Contactor sizing for compressors: poles, current and coil voltage.