Klima Industries

Klima Soft Copper Coil 5/8 in (15.88 mm), 1.0 mm Wall

Refrigeration-grade soft copper coil, 5/8 in outside diameter with 1.0 mm wall, 15 m.

Klima Copper Coils & Tubes ยท Model KCU-58-10

About this copper tube

From 5/8 in (15.88 mm) upwards the range moves to a 1.0 mm wall. The bore of this coil is 13.88 mm, about 151 ml per metre or roughly 2.3 litres in a 15 m coil, with a flow area more than eight times that of 1/4 in tube. It is soft (annealed) copper in a level-wound coil and is used as the gas (suction) line of systems of around 2.5 to 3 tons and for liquid lines on larger plant.

At this diameter the tube is heavier and stiffer, so bending by hand is not practical. A bender sized for 5/8 in is needed, and each bend should be formed in a single pass. The longer the run, the more important the gas-line size is: an undersized line adds pressure drop in the part of the circuit where the refrigerant is at its lowest density.

Specifications

SpecificationValue
ModelKCU-58-10
Size5/8 in
Outside diameter15.88 mm
Wall thickness1.0 mm
Length15 m
TemperSoft (annealed)
FormatLevel-wound coil

Where it fits

  • Gas line on larger split and ducted systems with 5/8 in connections
  • Suction line on medium condensing units and cold-room plant
  • Liquid line on larger packaged systems and chillers' auxiliary circuits
  • Extension of a line set where the original run was shortened

Fitting and checking

Braze with dry nitrogen flowing through the line, and use a torch with enough heat for the size so that the joint heats evenly and quickly. Fit insulation of the correct wall thickness and overlap the seams to stop condensation. When the line passes through a wall or floor, protect it with a sleeve and do not let it bear on masonry, where vibration and corrosion can damage it.

Compared with the other copper coils and tubes

The 6 models in Klima Copper Coils & Tubes differ mainly in size, outside diameter and wall thickness. Every model in the family has the same length (15 m), temper (Soft (annealed)) and format (Level-wound coil), so the choice comes down to the values above.

SpecificationThis modelAcross the range
Size5/8 in1/4 in / 3/8 in / 1/2 in / 5/8 in and 2 more
Outside diameter15.88 mm6.35 to 22.2 mm
Wall thickness1.0 mm0.8 to 1 mm

Ordered by outside diameter, this model is number 4 of 6: the next step down is Klima Soft Copper Coil 1/2 in (12.7 mm), 0.8 mm Wall (12.7 mm) and the next step up is Klima Soft Copper Coil 3/4 in (19.05 mm), 1.0 mm Wall (19.05 mm). Quote the model code KCU-58-10 when you enquire so that the right size is supplied.

Questions

Why does the wall get thicker at this size?

A larger tube must resist the same pressure over a bigger diameter, so the wall is increased to keep the hoop stress within limits. For 5/8 in tube many installers use 1.0 mm.

Is 15 m enough for a long run?

A coil can be joined with a brazed coupling, but every joint is a potential leak. Plan the route so that one length covers it where possible, and braze each joint with care.

Selection, care and fault-finding notes for the whole family are on the Klima Copper Coils & Tubes page, and the contact page takes enquiries with the model code KCU-58-10. For background reading, see the guide Brazing refrigerant pipe: flux, filler rods and map gas.